J-net Row HR2000 is a new generation of small intelligent micro-module data center solutions, integrating power distribution, UPS, monitoring, cooling, fire protection, lighting and cabinet and other systems. Among them, the infrastructure integrated cabinet integrates power distribution, UPS, refrigeration system, monitoring module, etc., which greatly saves the computer room space. IT cabinets flexibly expand on both sides of the infrastructure all-in-one cabinet, forming a single row of cold channels, providing an unprecedented excellent working environment and reliable guarantee platform for small and micro IT room Application Scenarios.
Send Message Get Price
| Single Row Configuration Table | |||
| Cabinet system | Cooling Generating Systems | ||
| Dimensions (H x W x D MM) | 2000(2200)X 600X 1400 | Rated AC input power supply | 380V AC 50Hz |
| Piping Type | Single row, cold channel | Cooling capacity (L35/L35) | 12.5KW |
| Number of single cabinets | 1-8 units | Rated Input Power | 3.5KW |
| Capacity | 42U (46U) * number of cabinets | Rated current | 19.5A |
| Protection Rating | IP30 | Heating Capacity | 3KW |
| Operating Temperature | -20℃~45℃ | Refrigerant | R410A |
| Installation | Concrete floor, raised floor | Sensitivity to heat ratio | ≥0.99 |
| Maximum load per cabinet | 6KW | Energy Efficiency Ratio | ≥3.2 |
| Supports maximum power consumption of IT load | 20KW | Air distribution | Front air supply, rear air return |
| IT cabinet bearing requirements | Static load 1500kg, dynamic load 1000kg | Installation | Inter-row installation |
| - Distribution System | ЧИСЛЕННОСТЬ ОБУЧАЮЩИХСЯ И УЧИТЕЛЕЙ В ГОСУДАРСТВЕННЫХ И МУНИЦИПАЛЬНЫХ ОБЩЕОБРАЗОВАТЕЛЬНЫХ ОРГАНИЗАЦИЯХ | ||
| Lightning protection level | Class C, In 20ka, Imax40ka | ЧИСЛЕННОСТЬ ОБУЧАЮЩИХСЯ И УЧИТЕЛЕЙ В ГОСУДАРСТВЕННЫХ И МУНИЦИПАЛЬНЫХ ОБЩЕОБРАЗОВАТЕЛЬНЫХ ОРГАНИЗАЦИЯХ | Support remote web interface access |
| Power Input | Single and dual channels optional | Local Interface | Standard 10-inch touch screen |
| Dual Power Switching System | Optional for 2-way input | Mobile O&M | Mobile App, SMS Alerts |
| UPS Capacity | 20KVA | Smoke detector | Optional |
| UPS Architecture | N,N+1,2N | Water immersion | Optional |
| Input Voltage | 380V Three Phase 3Ph + N + Pe | Temperature and humidity | Optional |
| Output voltage | 220V~240V AC 50Hz 380V~400V AC 50Hz |
door-lock | Optional |
| Output power factor | 0.9 | Video monitoring | Optional |
| Backup time | 15~30min | Fire Fighting System | |
| Repair bypass | Standard | Fire control cabinet | Heptafluoropropane pipe-free network digestion cabinet |
Note: Specifications are subject to change without prior notice for product improvement. Data Sheet
System Integration Functions
Highly available features
IT All-in-One Features
It is suitable for various power consumption scenar ios such as residential buildings and commercial office buildings
We're committed to providing prompt, professional support to ensure your energy needs are always met with the highest level of service.
We're here to answer your questions and provide the energy solutions that best fit your needs.