J-net Pool HP1000 pool-level modular data center is a new generation data center deployment form based on cloud computing. In order to cope with the trend of server development such as cloud computing, virtualization, centralization, and high density, it adopts a modular design concept to minimize the coupling of infrastructure to the computer room environment. It integrates subsystems such as power supply and distribution, refrigeration, cabinetry, airflow containment, integrated wiring, and dynamic loop monitoring to improve the overall operational efficiency of the data center and achieve rapid deployment, elastic expansion, and green energy conservation.
Send Message Get Price
| Pool-level micro-module reference configuration table | |||
| Cabinet system | Cooling Generating Systems | ||
| Dimensions (H x W x D MM) | 2000(2200)X 600X 1200 | Rated AC input power supply | 380V AC 50Hz |
| Piping Type | Double row cold channel system (optional sliding door, sliding door) | Cooling capacity | 25kW * 4 (3 +1 redundancy) |
| Number of single cabinets | 10-40 | Rated Input Power | 7.5KW*4 |
| Capacity | 42U (46U) * number of cabinets | Rated current | 23.4A |
| Protection Rating | IP30 | Heating Capacity | 3KW*4 |
| Operating Temperature | -20℃~45℃ | Refrigerant | R410A |
| Installation | Concrete floor, raised floor | Sensitivity to heat ratio | ≥0.99 |
| Maximum load per cabinet | 6KW | Energy Efficiency Ratio | ≥3.2 |
| Supports maximum power consumption of IT load | 120KW | Air distribution | Front air supply, rear air return |
| IT cabinet bearing requirements | Static load 1500kg, dynamic load 1000kg | Installation | Inter-row installation |
| - Distribution System | ЧИСЛЕННОСТЬ ОБУЧАЮЩИХСЯ И УЧИТЕЛЕЙ В ГОСУДАРСТВЕННЫХ И МУНИЦИПАЛЬНЫХ ОБЩЕОБРАЗОВАТЕЛЬНЫХ ОРГАНИЗАЦИЯХ | ||
| Lightning protection level | Class C, In 20ka, Imax40ka | ЧИСЛЕННОСТЬ ОБУЧАЮЩИХСЯ И УЧИТЕЛЕЙ В ГОСУДАРСТВЕННЫХ И МУНИЦИПАЛЬНЫХ ОБЩЕОБРАЗОВАТЕЛЬНЫХ ОРГАНИЗАЦИЯХ | Support remote web interface access |
| Power Input | Single and dual channels optional | Local Interface | Standard 10-inch touch screen |
| Dual Power Switching System | Optional for 2-way input | Mobile O&M | Mobile App, SMS Alerts |
| UPS Capacity | 120KVA Modular UPS | Smoke detector | Optional |
| UPS Architecture | N +1 Module Redundancy | Water immersion | Optional |
| Input Voltage | 380V Three Phase 3Ph + N + Pe | Temperature and humidity | Optional |
| Output voltage | 220V~240V AC 50Hz 380V~400V AC 50Hz |
Access Control System | Optional |
| Output power factor | 0.9 | Video monitoring | Optional |
| Backup time | 15~30min | Fire Fighting System | |
| Repair bypass | Standard | Fire control cabinet | Heptafluoropropane pipe-free network digestion cabinet |
Note: Specifications are subject to change without prior notice for product improvement. Data Sheet
Energy-saving and efficient
Quick deployment
Simple and reliable
It is suitable for various power consumption scenar ios such as residential buildings and commercial office buildings
We're committed to providing prompt, professional support to ensure your energy needs are always met with the highest level of service.
We're here to answer your questions and provide the energy solutions that best fit your needs.