AC row-end cabinet for equipment rooms; uses CTs to collect three-phase power data, supports multi-level alarm storage, and connects to facility power & environmental monitoring via Modbus.
Send Message Get Price
| Key Parameters | |
| Rated operating voltage | 380 V three-phase AC |
| Protection rating | ≥IP30 |
| Operating temperature | -5℃~55℃ |
| Dimensions | 600-1200 × 300-1200 × 2000-2600 mm |
| Parameter Category | Parameter Item | Specification |
|---|---|---|
| Electrical characteristics | Rated operating frequency | 50 Hz |
| Rated operating voltage | 380 V three-phase AC | |
| Rated insulation voltage | 690 V three-phase AC | |
| Rated impulse withstand voltage | ≥2.5 kV (50 Hz) | |
| Electrical surge protection | Imax=40 kA | |
| Pollution degree | Class III | |
| Protection rating | ≥IP30 | |
| Auxiliary circuit voltage | DC +24 V | |
| Operating environment | Operating temperature | -5℃~55℃ |
| Storage temperature | -20℃~+55℃ | |
| Operating relative humidity (30℃) | ≤80% | |
| Storage relative humidity (40℃±2℃) | 90%~96% | |
| Atmospheric pressure | 65~110 kPa | |
| Cabinet dimensions | External dimensions | (600-1200)×(300-1200)×(2000-2600) mm |
| Ordering options | External dimensions | Customizable |
| Front/rear door style | Single front & rear / double front & rear / single front / double front | |
| Frame sheet thickness | Customizable | |
| Protection rating | ≥IP30 | |
| Cabinet paint color | Customizable | |
| Input current / circuits | Configured as required | |
| Output current / circuits | Configured as required | |
| Monitoring functions | Input monitoring / full input-output monitoring / with digital I/O monitoring |
Note: Specifications are subject to change without prior notice for product improvement. Data Sheet
Breakers + copper busbars with orderly circuit layout for stable, reliable supply
CTs collect three-phase voltage, current, power, and energy for full-dimensional data
Customizable Level-2 over-limit and trip alarms with local storage for traceability
RS485 Modbus + Ethernet upload, compatible with mainstream facility monitoring systems
It is suitable for various power consumption scenar ios such as residential buildings and commercial office buildings
We're committed to providing prompt, professional support to ensure your energy needs are always met with the highest level of service.
We're here to answer your questions and provide the energy solutions that best fit your needs.