The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management-including low-voltage protection and optional load disconnect-plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Send Message Get Price
| Environmental Parameters | Operating conditions | Transport conditions | Storage conditions | Applicable standards | Remarks | |||
| Category | Parameter | Unit | ||||||
| Climatic conditions | Temperature | Low temperature | ℃ | -33 | -40 | -40 | YD/T 1058-2000 Clauses 4.1.1 and 4.1.2 | Full-load start at −40℃; linear 20% derating from +55 to +65℃. |
| High temperature | ℃ | 65 | 70 | 70 | ||||
| Temperature change | ℃/min | / | 1 | / | ETS 300 019-2-2 T2.3 | |||
| Operating ambient temperature | ℃ | -33-65 | Full-load extreme operating temperature | |||||
| Storage temperature | ℃ | -40-70 | ||||||
| Humidity | Relative humidity | % | 5-90 | 90 (40±2℃) | / | YD/T 1058-2000 Clause 4.1.3 | Short-term test: 0-95%, max 95%, non-condensing | |
| Condensation | Yes/No | No | No | Yes | ||||
| Atmospheric pressure | Low pressure | kPa | 86 | 70 | 70 | YD/T 1058-2000 Clause 4.1.4 | Module testing only | |
| High pressure | kPa | 106 | 106 | 106 | ||||
| Altitude | m | ≤4000 | Above 2000 m, derate 0.5℃ per additional 100 m | |||||
Note: Specifications are subject to change without prior notice for product improvement. Data Sheet
Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring
Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX
High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms
Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing
Equipotential design across the cabinet improves EMC and lightning protection
It is suitable for various power consumption scenar ios such as residential buildings and commercial office buildings
We're committed to providing prompt, professional support to ensure your energy needs are always met with the highest level of service.