Outdoor integrated smart cabinet solution for ETC gantry systems. The cabinet integrates air-conditioning, power systems, battery backup, fire safety, power distribution modules, and intelligent monitoring, with reserved space for customer switches and ETC service equipment, providing a reliable operating environment for ETC gantry devices above highway mainlines.
Send Message Get Price
| ETC Gantry Integrated Smart Cabinet | ||||
| No. | Item | Specification | Qty | Remarks |
| 1 | Integrated cabinet | Dual bay 1800*1600*900 aluminum-profile frame + composite panel structure | 1 | Includes lighting, racks, grounding, battery racks, etc. |
| 2 | Power distribution unit | 4U rack-mount; mains/genset transfer and surge protection | 1 | Dual input (mains, genset) |
| 3 | Air conditioner | 1500 W AC | 2 | 1 set per bay |
| 4 | Smart electronic lock | Type 864 | 2 | |
| 5 | PDU | AC 220 V, 6-outlet GB national standard | 1 | |
| 6 | UPS power system | 10 kVA power supply, 10U | 1 | |
| 7 | LiFePO4 battery | 240 V 100 AH | 4 | Lead-acid batteries optional |
| 8 | ODF unit | 24-core ODF fiber distribution frame | 1 | |
| 9 | Power & environment monitoring unit | Multi-channel DI/DO interfaces | 1 | Water leak, temperature/humidity, smoke detectors, etc. |
| 10 | Smart lock | Passive | 1 | Includes 1 electronic key |
| 11 | Switch | 24-port full Gigabit PoE rack-mount | 1 | |
| 12 | Video capture | Host, sensors, etc. | 1 | |
| 13 | Power & environment monitoring unit | 220 V | 1 | |
Note: Specifications are subject to change without prior notice for product improvement. Data Sheet
Welded sheet-metal frame with high structural strength; dual-layer construction: 20 mm EPS insulation, inner layer 0.8 mm steel sheet
Bottom cable entry with 4 cable glands for power, fiber, and copper cables; interior fitted with uprights, shelves, door magnetic sensors, installation accessories, etc
Anti-theft design with three-point locking; fasteners are inside the cabinet and not visible externally to prevent unauthorized disassembly
degreasing, pickling, anti-rust phosphating, electrostatic powder coating; outdoor cabinets use imported outdoor powder baked finish compliant with GB/T 3181-2008
Supports 19-inch (IEC 297) standard racks and equipment meeting 19-inch (IEC 297) mounting space requirements
Ingress protection IP55 or above; high integration and compact structure for easy installation and later relocation
Multi-layer protection including access control, smoke, water ingress, temperature/humidity, and impact detection
It is suitable for various power consumption scenar ios such as residential buildings and commercial office buildings
We're committed to providing prompt, professional support to ensure your energy needs are always met with the highest level of service.